RB-KY Multi-channel Gas Alarm Control Unit
 

Main Features:

  • 1-12 channel capacity
  • 4-20mA standard signal input, output
  • Warm-up without alarm and automatic zero calibration
  • High, low alarm setting and adjustable alarm setting value
  • Self Trouble Diagnosis and Remedy
  • Indicate the gas concentration in digital display
  • Manual operation for the fan, valve

 

Main Specifications:

Measuring Range

0-100%LEL

Sound Volume

≥70dB

Alarm Method

Audio and Visual

Power

AC 220V±15% 50HZ (DC24V Spare Power)

Display

Digital

Operation Environment

Temperature: -10℃~+50℃

Low Alarm

20%LEL(Adjustable)

Relative Humidity: <93%R.H

High Alarm

50%LEL

Dimensions

RB-KY-1/2/3450×230×93mm

RB-KY-4/5450×320×93mm

RB-KY-6/7450×410×93mm RB-KY-8/9450×500×93mm

Response Time

≤30S

Accuracy

≤±5% F.S

Alarm Output

220V 1A

 

  